  1.     SECTION 07615
  2.  
  3.     PROTECTED LEAD MEMBRANE ROOFING
  4. NOTE ** This section is based on products manufactured by members of the Lead Industries Association, Inc., at the following address:
  5. NOTE **      295 Madison Avenue
  6. NOTE **      New York, NY  10017
  7. NOTE **      Telephone 212-578-4750
  8. NOTE **      Fax 212-684-7714
  9. NOTE ** 
  10. NOTE ** Lead waterproofing has long been used for plazas, fountains, pools, and other applications on outstanding buildings such as the World Trade Center and the United Nations Library.
  11. NOTE ** 
  12. NOTE ** Now, in combination with extruded polystyrene insulation panels, flat roofs with impressive lifetime-cycle performance are being constructed.
  13. NOTE ** 
  14. NOTE ** SECTION 07615 - PROTECTED LEAD MEMBRANE ROOFING, Copyright 1996, The Architect's Catalog, Inc.
  15.  
  16.  
  17. PART 1    GENERAL
  18.  
  19. 1.1    SECTION INCLUDES
  20. NOTE ** Delete items below not required for project.
  21.  
  22.     A.    Continuous, welded lead sheet membrane roofing.
  23.  
  24.     B.    Insulation.
  25.  
  26.     C.    Insulation ballast.
  27.  
  28.     D.    Counterflashings for lead roofing.
  29.  
  30.     E.    Penetration flashings and perimeter flashings for lead roofing.
  31.  
  32. 1.2    RELATED SECTIONS
  33. NOTE ** Delete any sections below not relevant to this project;  add others as required.
  34.  
  35.     A.    Section 03300 - Cast-In-Place Concrete.
  36.  
  37.     B.    Section 06100 - Rough Carpentry.
  38.  
  39.     C.    Section 07152 - Lead Membrane Waterproofing.
  40.  
  41.     D.    Section 07600 - Flashing and Sheet Metal.
  42.  
  43. 1.3    REFERENCES
  44. NOTE ** Delete references from the list below that are not actually required by the text of the edited section.
  45.  
  46.     A.    ASTM A 167 - Standard Specification for Stainless and Heat-Resisting Chromium Nickel Steel Plate, Sheet, and Strip.
  47.  
  48.     B.    ASTM A 666 - Standard Specification for Austenitic Stainless Steel, Sheet, Strip, Plate, and Flat Bar.
  49.  
  50.     C.    ASTM B 749 - Standard Specification for Lead and Lead Alloy Strip, Sheet, and Plate Products.
  51.  
  52.     D.    ASTM C 578 - Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation.
  53.  
  54.     E.    ASTM D 226 - Standard Specification for Asphalt Saturated Organic Felt Used in Roofing and Waterproofing.
  55.  
  56.     F.    Flat Roofing Brochure - Lead Industries Association, Inc.  (LIA).
  57.  
  58. 1.4    SUBMITTALS
  59.  
  60.     A.    Submit under provisions of Section 01300.
  61.  
  62.     B.    Product Data:  Provide manufacturer's standard details and catalog data demonstrating compliance with referenced standards.  Provide installation instructions.
  63.  
  64.     C.    Samples:
  65.         1.    6 x 6 inch samples of sheet lead.
  66.         2.    Samples of insulation board.
  67.         3.    Ballast samples.
  68.         4.    Stainless steel strip for insulation ballasting.
  69.  
  70. 1.5    QUALITY ASSURANCE
  71.  
  72.     A.    Installer Qualifications:  Employ only qualified journeymen lead burners to join sheets of lead.
  73.  
  74. 1.6    DELIVERY, STORAGE, AND HANDLING
  75.  
  76.     A.    Handle, store, and protect lead from deformation, construction traffic, and damage.
  77.  
  78.     B.    Handle, store and protect insulation in accordance with manufacturer's instructions.
  79.  
  80.  
  81. PART 2    PRODUCTS
  82.  
  83. 2.1    MEMBRANE MATERIALS
  84.  
  85.     A.    Sheet Lead:
  86.         1.    Comply with ASTM B 749.
  87.         2.    Weight:  5 psf (5/64-inch thick) minimum.
  88.         3.    Furnish in 8 x 25 foot rolls, unless otherwise required or approved.
  89.  
  90.     B.    Burning Rods:  Same composition as sheet lead.
  91.  
  92.     C.    Underlayment:  15 lb. asphalt-impregnated felt;  ASTM D 226, Type I.
  93.  
  94.     D.    Slip Sheet:  Reinforced plastic or paper such as "Tyvek," "Visquine," etc.
  95.  
  96.     E.    Temporary Protection Board:  At least one, 1/2-inch thick layer of any suitable particle board or plywood.
  97.  
  98. 2.2    COUNTERFLASHING MATERIALS
  99. NOTE ** Delete 1 of the 2 following paragraphs, and edit gage to suit project conditions.
  100.  
  101.     A.    Stainless Steel:  ASTM A 167, Type 304, 28 gage unless otherwise indicated.
  102.  
  103.     B.    Lead-Coated Stainless Steel:  ASTM A 167, Type 304, 28 gage prior to coating unless otherwise indicated.
  104.  
  105. 2.3    INSULATION MATERIALS
  106.  
  107.     A.    Insulation:  Extruded polystyrene, ASTM C 578, Type VI.
  108.         B.    Compressive strength:  40 psi minimum.
  109.         1.    Tongue and grooved edges on two sides.
  110.         2.    Drainage channels on surface in contact with roofing membrane.
  111. NOTE ** Edit the 3 following paragraphs to suit project requirements.
  112. NOTE ** 
  113. NOTE ** Either single or double-layer installation may be employed.  In double-layer systems, bottom layer thickness must be at least 2 inches thick, and must be the thicker of the two layers.
  114. NOTE ** 
  115. NOTE ** Select thickness to provide an R-value that will maintain the lead membrane at a near constant temperature (R-15 minimum).
  116. NOTE ** 
  117. NOTE ** See foam manufacturer's literature for additional thicknesses available.
  118.         3.    Bottom layer foam thickness:  2 inches.
  119.         4.    Top layer foam thickness:  1-1/2 inches.
  120.         5.    Foam thickness:  3 inches.
  121. NOTE ** Foam insulation must be protected from U.V. exposure and secured against wind uplift by 1 of 4 accepted methods, which are:
  122. NOTE **   -  Foam panels with integral factory-facing of cement mortar.
  123. NOTE **   -  Placing stone ballast on top of foam.
  124. NOTE **   -  Placing roofing pavers on top of foam.
  125. NOTE **   -  A combination of roofing pavers (at perimeters and as walkways) with
  126. NOTE **      stone ballast over remainder.
  127. NOTE ** 
  128. NOTE ** Insulation with integral factory-facing of cement mortar is generally restrained at perimeters and penetrations by stainless steel straps and securement devices or by roofing pavers and relies upon tongue and groove edges to prevent uplift of field boards. 
  129. NOTE ** 
  130. NOTE ** Delete the following paragraph if insulation with integral facing of cement-mortar is not required.
  131.         6.    Integral mortar facing:  Latex-modified Portland cement mortar weighing 4.5 psf.
  132.             a.    Facing thickness:  3/8 inch mortar facing (in addition to foam thickness).
  133. NOTE ** Delete the following paragraphs, including separation sheet, if stone or paver ballast materials are not required.
  134. NOTE ** 
  135. NOTE ** If used, edit to suit project requirements.
  136.  
  137.     C.    Separation Sheet:  As recommended by insulation manufacturer.
  138.  
  139.     D.    Ballast:
  140.         1.    Aggregate:  Sound, hard, durable stone;  ASTM D 448, No. 4, free of dirt, debris, and other deleterious matter.
  141.         2.    Select aggregate:  As above, except screened to 1 inch minimum to 1-1/2 inch maximum.
  142. NOTE ** A variety of additional paver designs are available.  Those specified below have been selected primarily for use as walkways and perimeter securement of aggregate ballasted installations, and for perimeter securement of mortar-faced foam installations.  See foam and paver manufacturer's literature for additional requirements and design criteria.
  143. NOTE ** 
  144. NOTE ** For designs with full coverage with pavers, see foam manufacturer's recommendations for air space between foam and pedestals.  
  145.         3.    Pavers:  Normal weight concrete paver units manufactured for use as roof ballast.
  146.             a.    Weight:  At least 15 psf.
  147.             b.    Compressive strength:  At least 7,500 psi.
  148. NOTE ** Specify color, below, or delete if immaterial.
  149.             c.    Color:  _______________.
  150. NOTE ** Edit size, below, to suit project requirements, or delete entirely other applications where size is immaterial.
  151.             d.    Size:  24 x 24 inches.
  152.             e.    Size:  18 x 18 inches.
  153.             f.    Size:  12 x 18 inches.
  154.             g.    Size:  12 x 12 inches.
  155.  
  156. 2.4    MISCELLANEOUS MATERIALS
  157. NOTE ** Delete 1 of the 2 following paragraphs.
  158.  
  159.     A.    Cants:  Concrete cants specified in Division 3.
  160.  
  161.     B.    Cants:  Pressure-preservative-treated wood specified in Division 6.
  162. NOTE ** A variety of metal securement devices are available for mortar-faced insulation units.  Consult manufacturer's literature.
  163. NOTE ** 
  164. NOTE ** Delete the following paragraph if not required.
  165.  
  166.     C.    Insulation Securement:  ASTM A 666 stainless steel straps and securement devices, as recommended by insulation manufacturer.
  167.  
  168.  
  169. PART 3    EXECUTION
  170.  
  171. 3.1    EXAMINATION
  172.  
  173.     A.    Examine surfaces to receive sheet lead roofing.
  174.         1.    Verify that surfaces are smooth and even, free of projections, protrusions, or other irregularities.
  175.         2.    Verify that angles and edges over which lead will be turned are chamfered or eased.
  176.         3.    Verify that cants are securely installed.
  177.         4.    Do not begin roofing operations until surrounding or abutting construction and penetrations through roofing are completed and approved.
  178. NOTE ** Delete the following paragraph if concrete roof deck is not used.
  179. NOTE ** 
  180. NOTE ** When retrofitting lead roofing over existing substrates, an additional underlayment surface such as gypsum board or plywood may be necessary, and should be included in this or another specification section.
  181.  
  182.     B.    Cementitious Substrates:
  183.         1.    Verify that concrete is sound, clean, and free of dirt, dust, debris, or other contaminants.
  184.         2.    Verify that concrete surfaces have been screeded and floated to a smooth surface without projecting stones or other aggregate.
  185.         3.    Verify that brick or other masonry substrates are laid true and straight, with joints struck flush or tooled with half-round tool.
  186.  
  187.     C.    Notify the Architect in writing of any defective conditions encountered.
  188.  
  189.     D.    Correct defective conditions before beginning waterproofing work.  Starting of work shall constitute acceptance of such conditions.
  190.  
  191. 3.2    SURFACE PREPARATION
  192. NOTE ** Delete the 3 following paragraphs if cementitious substrates are not used.
  193.  
  194.     A.    Grind down high spots.
  195.  
  196.     B.    Fill low spots with Portland-cement-based patching compound approved by the Architect.
  197.  
  198.     C.    Parge irregular substrates with acrylic-latex modified Portland-cement-based mortar approved by the Architect.
  199.  
  200.     D.    Install 1 layer of underlayment over entire surface to be waterproofed.  Install 1 layer of slip sheet over underlayment.
  201.  
  202. 3.3    MEMBRANE INSTALLATION
  203.  
  204.     A.    Lay out sheet to minimize joints.
  205.  
  206.     B.    Lap joints between adjoining sheets 1-1/2 inches minimum.
  207.  
  208.     C.    Tools, brakes, tongs, etc., shall be such as to bend and work lead to easy curves and to prevent scoring or damaging the material.  Only proper lead working tools (wooden mallets, dressers, etc). are acceptable to form the lead.
  209.  
  210.     D.    Allow room for expansion between rigid members.
  211.  
  212. 3.4    JOINTS
  213.  
  214.     A.    Clean by shave hook, lead scraper, or wire brush, sections of lead that are to become a part of the joint.
  215.  
  216.     B.    Join adjacent pieces of lead sheet by burning (welding of lead to lead).
  217.         1.    Use only the smallest size tip on burning torch.
  218.         2.    Use only hydrogen and oxygen gases only.
  219.         3.    Take extreme care to avoid burning through or reducing the thickness of the lead sheet being joined.
  220.  
  221. 3.5    FLASHINGS
  222.  
  223.     A.    Install lead sheet base flashings integrally with roofing membrane.
  224.         1.    Extend to top of and across parapets, unless otherwise indicated.
  225.         2.    Where membrane terminates at vertical walls, terminate flashing in reglet.
  226.  
  227.     B.    Install stainless steel counterflashings as indicated.
  228.  
  229.     C.    At penetrations, install lead sheet flashings and burn same to membrane.
  230.         1.    Comply with details and recommendations of LIA Flat Roofing Brochure, unless otherwise indicated.
  231.  
  232. 3.6    INSULATION
  233.  
  234.     A.    Install insulation in accordance with insulation manufacturer's instructions for protected membrane roofing.
  235.  
  236.     B.    Cut neatly to fit around projections and penetrations and at perimeter.
  237. NOTE ** Delete 1 of the 2 following paragraphs when mortar-faced insulation is used.
  238. NOTE ** 
  239. NOTE ** Delete both if mortar-faced insulation is not used.
  240.  
  241.     C.    Secure perimeters of and penetrations through mortar-faced insulation with pavers.
  242.  
  243.     D.    Mechanically fasten mortar-faced insulation with stainless steel securement devices in accordance with manufacturer's instructions.
  244. NOTE ** Delete the following article if insulation with integral mortar facing is used exclusively.
  245.  
  246. 3.7    BALLAST
  247.  
  248.     A.    Install separation sheet in accordance with insulation manufacturer's instructions.
  249. NOTE ** Delete one or both of the following paragraphs, as required by project conditions.
  250.  
  251.     B.    Install roof pavers over entire surface.  Cut neatly to fit around projections and penetrations and at perimeter.
  252.  
  253.     C.    Install roof pavers in the locations indicated on the drawings.  Cut neatly to fit around projections and penetrations and at perimeter.
  254. NOTE ** Delete the following paragraph if aggregate ballast is not used.
  255. NOTE ** 
  256. NOTE ** Aggregate rate is dependent upon aggregate size, building height, and wind conditions.  Consult foam manufacturer's literature for additional information, and edit the following paragraphs to suit project conditions.
  257.  
  258.     D.    Install aggregate ballast at the rate so as to ensure complete coverage of foam, and blockage of U.V. light.
  259.         1.    Use at least 10 pounds of aggregate per square foot.
  260.         2.    Within 4 feet of perimeter, penetrations, and drains, use at least 20 pounds of aggregate per square foot.
  261.         3.    Use select aggregate around drains.
  262.  
  263. 3.8    PROTECTION
  264.  
  265.     A.    Protect material and work in place from damage.  Repair any damage that may occur.
  266.  
  267.     B.    Provide temporary water cut-offs to prevent penetration of water underneath the membrane when work is interrupted, at end of day, or during inclement weather.  Remove and discard temporary cut-offs before proceeding.
  268.  
  269.     C.    Temporary Protection:  Do not permit construction traffic directly on top of lead sheet.  Install suitable protection board as installation proceeds to guard against occasional, essential light traffic and against excessive temperature changes until permanent covering has been installed.